The choice of line size 

Electrical wiring must meet the requirements of safety, reliability and cost. It is therefore important to correctly calculate the length and cross section required for the installation of electrical wiring cables.

The length of wire is calculated on the circuit diagram. For this scheme to measure the distance between adjacent locations boards, plug sockets, switches, branch boxes, etc. Then, using the scale at which the drawn diagram, calculate the length of wire segments, the length of each segment to add at least 100 mm (recorded the need for adherence of wires). The length of wire can be calculated also by measuring directly on the panel, panels, walls, ceilings, etc. sections of the lines along which the wires must be laid.

Cross section of wire is calculated on the loss of voltage and current, valid long-term load. If the calculated cross section will vary, for the final result are larger than a cross-section.

The loss of voltage due to voltage drop in the wires that connect the source of electric current with the receiver. It should not exceed 2 - 5% of nominal voltage power supply. The cross-section of wires in a loss of voltage is calculated in the design of electrical networks, which feed electricity receivers industries, transport, major residential and public buildings, etc.

In the design of small electrical installations, electrical installations such as individual rooms, improvised devices, etc., loss of tension in the wires can be neglected, because it is very small.

To calculate the cross section of the wires on the permissible long-term need to know the current load rated current, which should be designed for electrical wiring. Knowing the rated current, the cross section of wire is on the table.

Section
conductive
veins, mm2

Current to the wires and cables with copper veins, A

Current to the wires and cables with aluminum threaded, A

One-

Double

Three vein

One-

Double

Three vein

When laying
air
air

Land

air

Land

air
air

Land

air

Land

1,5

23

19

33

19

27

-

-

-

-

-

2,5

30

27

44

25

38

23

21

34

19

29

4

41

38

55

35

49

31

29

42

27

38

6

50

50

70

42

60

38

38

55

32

46

10

80

70

105

55

90

60

55

80

42

70

16

100

90

135

75

115

75

70

105

60

90

25

140

115

175

95

150

105

90

135

75

115

35

170

140

210

120

180

130

105

160

90

140

50

215

175

265

145

225

165

135

205

110

175

70

270

215

320

180

275

210

165

245

140

210

95

325

260

385

220

330

250

200

295

170

255

120

385

300

445

260

385

295

230

340

200

295

150

440

350

505

305

435

340

270

390

235

335

185

510

405

570

350

500

390

310

440

270

385

240

605

-

-

-

-

465

-

-

-

-